Abstract


This research was conducted to analyze electricity supply availability from the steam power plant at PLN Teluk Sirih. This electricity supply availability is also called the equivalent availability factor (EAF). The regular efforts made to maintain the EAF at PLN are still corrective, by repairing the damage that has occurred, and no systematic method has been implemented. Accurate analysis is required to achieve high EAF values and precision so that the problem's root cause can be resolved. This can be done by using the lean six sigma method. This method can identify waste and solve problems quickly. The methodology used is Define, Measure, Analyze, Improve, and Control (DMAIC). The waste that occurs is a defect, which is the inability of the power plant to supply electricity to customers (PLN P3BS). The identification results show that the factors that influence EAF are boiler tube leak (41.46%), DS Phase S (20.45%), equipment vibration (5.85%), bottom ash system (5.39%), and other disorders (26.84%). The EAF calculation for the last two years is 70.93%, and the six sigma level is 2.05. The improvement design is expected to eliminate boiler tube leak and increases the EAF by 6.65%. Thus, the EAF value becomes 77.85%, and the six sigma level becomes 2.26.


Keywords


Faktor Ketersediaan Ekuivalen (EAF); Lean Six Sigma; Pemborosan; Metode DMAIC; Pembangkit Listrik Tenaga Uap

Full Text:

PDF

References


Staff Analyst Kinerja, “Laporan Kinerja dan Pengusahaan Desember 2019 & Kontrak Manajemen Tahun 2020,” Dept. Enjiniring, Padang, Sumatera Barat, 2020.

NERC, “Electronic GADS Generating Availability Report”, The North American Electric Reliability Corporation, Atlanta, Georgia, 2012.

Y. Obergfell, “Six Sigma,” Six Sigma Revealed, 2nd ed. Wollerau, Switzerland, International Six Sigma Institute, 2014, ch. 3, sec. 1, pp. 10.

S.L. Furterer, “Lean Six Sigma Case Study Goals,” Lean Six Sigma in Service - Applications and Case Studies, 1st ed. Boca Raton, CRC Press, 2009, ch. 1, sec. 3, pp. 1-2.

Adriyansyah, A. Sutanto and B. Yuliandra, “Aplikasi konsep produksi ramping untuk memperbaiki efisiensi pengolahan minyak kelapa sawit”, Jurnal Energi dan Manufaktur, Vol. 11 No.2, pp. 36-41, Oktober, 2018

S.K. Dhua, “Metallurgical investigation of failed boiler water-wall tubes received from a thermal power station,” Engineering Failure Analysis, Vol. 17, No. 7, pp. 1572-1579, Oktober, 2010.

S.S. Prabu, A. Choudhary, N. Mittal, S. Gupta, D. Ramkumar and A. Natarajan, “Failure evaluation of SA 210C riffle water wall tubes in 70MW CFBC boiler,” Engineering Failure Analysis, Vol. 95, pp. 239–247, Januari, 2019.

C.A. Duarte, E. Espejo and J.C. Martinez, “Failure analysis of the wall tubes of a water-tube boiler,” Engineering Failure Analysis, Vol. 79, pp. 704–713, September, 2017.

Y.S. Kim, W.C. Kim and J.G. Kim, “Bulging rupture and caustic corrosion of a boiler tube in a thermal power plant,” Engineering Failure Analysis, Vol. 104, pp. 560–567, Oktober, 2019.

C. Yu, W. Xiong, H. Ma, J. Zhou, F. Si, X. Jiang and X. Fang, “Numerical investigation of combustion optimization in a tangential firing boiler considering steam tube overheating,” Applied Thermal Engineering, Vol. 154, pp. 87–101, Mei, 2019.

M. Nad, Z. Jegla, T. Létal, P. Lošák and J. Buzik, “Thermal load non-uniformity estimation for superheater tube bundle damage evaluation,” MATEC Web of Conferences, Vol. 157, no. 2033, Maret, 2018.